Rheem Performance XG55T06EN45U0 Instruction Manual Page 11

  • Download
  • Add to my manuals
  • Print
  • Page
    / 28
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 10
11
WARNING: DO NOT
attempt to convert this
water heater for use with
a different type of gas
other than the type shown
on the rating plate. Such
conversion could result in
hazardous operating
conditions.
Pressure Testing the Gas Supply System
The appliance and its individual shutoff
valve must be disconnected from the gas
supply piping system during any pressure
testing of that system at test pressures in
excess of 1/2 psi (3.5 kPa).
The appliance must be isolated from the
gas supply piping system by closing its
individual manual shutoff valve during
any pressure testing of the gas supply
piping system at test pressures equal to or
less than 1/2 psi (3.5 kPa).
Gas Supply
The branch gas supply line to the water
heater should be clean 1/2” black steel
pipe or other approved gas piping
material.
A ground joint union or ANSI design
certified semi-rigid or flexible gas
appliance connector should be installed
in the gas line close to the water heater.
The National Fuel Gas Code (NFGC)
mandates a manual gas shut-off valve: See
(NFGC) for complete instructions.
If flexible connectors are used, the
maximum length shall not exceed 36”.
Compound used on the threaded joints of
the gas piping must be of the type resistant
to the action of LP gas. Use compound
sparingly on male threads only.
Where a sediment trap is not incorporated
as part of the appliance, a sediment trap
shall be installed downstream of the
equipment shutoff valve as close to the
inlet of the appliance as practical at the
time of the appliance installation. The
sediment trap shall be either a tee fitting
with a capped nipple in the bottom outlet
or other device recognized as an effective
sediment trap. DO NOT use excessive
force (over 31.5 ft lbs.) in tightening the
pipe joint at the gas control (thermostat)
inlet, particularly if teflon pipe compound
is used, as the valve body may be
damaged.
The inlet gas pressure to the water heater
must not exceed 10.5” w.c. for natural gas,
or 14” w.c. for LP gas. For purposes of
input adjustment, the minimum inlet gas
pressure (with main burner on) is shown
on the water heater rating plate. If high or
low gas pressures are present, contact your
gas supplier for correction.
Leak Testing
The water heater and its gas connections
must be leak tested at normal operating
pressures before it is placed in operation.
Turn on the manual gas shut-off
valve near the water heater.
Use a soapy water solution to test for
leaks at all connections and fittings.
Bubbles indicate a gas leak that must
be corrected.
The factory connections to the gas
control (thermostat) should also be leak
tested after the water heater is placed in
operation.
WARNING: Never use
an open flame to test for
gas leaks, as property
damage, personal injury, or
death could result.
High Altitude
This water heater is certified for
installations up to 10,200 feet above sea
level.
!
WARNING: Installations above
10,200 feet are not authorized and may
result in improper and inefficient
operation of the appliance, producing
carbon monoxide gas in excess of
acceptable limits, which could result in
serious injury or death.
WARNING: Failure to
install a water heater
suitable for the altitude at
the location it is intended to
serve, can result in improper
operation of the appliance
resulting in property
damage and/or, producing
carbon monoxide gas, which
could result in personal
injury, or death.